Recloser information


Four reclosers on the right side of a substation

In electric power distribution, automatic circuit reclosers (ACRs) are a class of switchgear designed for use on overhead electricity distribution networks to detect and interrupt transient faults. Also known as reclosers or autoreclosers, ACRs are essentially rated circuit breakers with integrated current and voltage sensors and a protection relay, optimized for use as a protection asset. Commercial ACRs are governed by the IEC 62271-111/IEEE Std C37.60 and IEC 62271-200 standards.[1][2] The three major classes of operating maximum voltage are 15.5 kV, 27 kV and 38 kV.

For overhead electric power distribution networks, up to 80% of faults are transient, such as lightning strike, surges or foreign objects coming into contact with exposed distribution lines. Consequently, these transient faults can be resolved by a simple reclose operation.[3] Reclosers are designed to handle a brief open-close duty cycle, where electrical engineers can optionally configure the number and timing of attempted close operations prior to transitioning to a lockout stage.[4] The number of reclose attempts is limited to a maximum of four by recloser standards noted above.

At two multiples of the rated current, the recloser's rapid trip curve can cause a trip (off circuit) in as little as 1.5 cycles (or 30 milliseconds). During those 1.5 cycles, other separate circuits can see voltage dips or blinks until the affected circuit opens to stop the fault current. Automatically closing the breaker after it has tripped and stayed open for a brief amount of time, usually after 1 to 5 seconds, is a standard procedure.[5]

Reclosers are often used as a key component in a smart grid, as they are effectively computer controlled switchgear which can be remotely operated and interrogated using supervisory control and data acquisition (SCADA) or other communications. Interrogation and remote operation capabilities allow utilities to aggregate data about their network performance, and develop automation schemes for power restoration. Automation schemes can either be distributed (executed at the remote recloser level) or centralized (close and open commands issued by a central utility control room to be executed by remotely controlled ACRs).

  1. ^ "IEC 62271-111:2019 Automatic circuit reclosers for alternating current systems up to and including 38 kV". webstore.iec.ch. Retrieved 25 June 2022.
  2. ^ IEC/IEEE International Standard - High-voltage switchgear and controlgear - Part 111: Automatic circuit reclosers for alternating current systems up to and including 38 kV. February 2019. pp. 1–272. doi:10.1109/IEEESTD.2019.8641507. ISBN 978-2-8322-4991-8. Retrieved 25 June 2022. {{cite book}}: |journal= ignored (help)
  3. ^ B. M. Weedy (1972), Electric Power Systems (Second ed.), London: John Wiley and Sons, p. 26, ISBN 978-0-471-92445-6
  4. ^ Thompson, Stan. "Auto-Recloser - Safety and Minimising Downtime". Transmission & Distribution Issue 1 2018. Retrieved 2018-07-02.
  5. ^ Jeremy Blair, Greg Hathway, and Trevor Mattson of Schweitzer Engineering Laboratories, Inc. "Solutions to Common Distribution Protection Challenges".{{cite web}}: CS1 maint: multiple names: authors list (link)

and 24 Related for: Recloser information

Request time (Page generated in 0.5512 seconds.)

Recloser

Last Update:

In electric power distribution, automatic circuit reclosers (ACRs) are a class of switchgear designed for use on overhead electricity distribution networks...

Word Count : 2154

Intelligent electronic device

Last Update:

changer controllers, circuit breaker controllers, capacitor bank switches, recloser controllers, voltage regulators etc. This is generally controlled by a...

Word Count : 311

Electric power conversion

Last Update:

Interconnector Demand response Electric power systems components Ring main unit Grid-tie inverter Energy storage Busbar Bus duct Recloser Protective relay v t e...

Word Count : 971

Busbar

Last Update:

Interconnector Demand response Electric power systems components Ring main unit Grid-tie inverter Energy storage Busbar Bus duct Recloser Protective relay v t e...

Word Count : 753

Power station

Last Update:

Interconnector Demand response Electric power systems components Ring main unit Grid-tie inverter Energy storage Busbar Bus duct Recloser Protective relay v t e...

Word Count : 5179

Electrical substation

Last Update:

currents that may occur on the network. Smaller distribution stations may use recloser circuit breakers or fuses for protection of distribution circuits. Substations...

Word Count : 3054

Electronic component

Last Update:

Lightning arrester – spark gap used to protect against lightning strikes Recloser – automatic switch that opens on an overcurrent (fault) condition, then...

Word Count : 2712

Electrical grid

Last Update:

Interconnector Demand response Electric power systems components Ring main unit Grid-tie inverter Energy storage Busbar Bus duct Recloser Protective relay v t e...

Word Count : 7109

Hydraulic machinery

Last Update:

(1990). Chemical Reactor Analysis and Design. "Reclosers: maintenance instructions". Section ""Recloser operation". p. 3-4. "What Do Hydraulic Filters...

Word Count : 4816

HVDC converter station

Last Update:

Interconnector Demand response Electric power systems components Ring main unit Grid-tie inverter Energy storage Busbar Bus duct Recloser Protective relay v t e...

Word Count : 1236

Circuit breaker

Last Update:

person on the ground or via plumbing. (also called VOELCB in the UK). Recloser — A type of circuit breaker that closes automatically after a delay. These...

Word Count : 4908

Power engineering

Last Update:

Interconnector Demand response Electric power systems components Ring main unit Grid-tie inverter Energy storage Busbar Bus duct Recloser Protective relay v t e...

Word Count : 1888

Electric power system

Last Update:

alternatively, can focus on systemic improvements: such as the installation of reclosers on sections of the system that are subject to frequent temporary disruptions...

Word Count : 6274

Rectifier

Last Update:

Interconnector Demand response Electric power systems components Ring main unit Grid-tie inverter Energy storage Busbar Bus duct Recloser Protective relay v t e...

Word Count : 8946

Electricity generation

Last Update:

Interconnector Demand response Electric power systems components Ring main unit Grid-tie inverter Energy storage Busbar Bus duct Recloser Protective relay v t e...

Word Count : 5830

Voltage converter

Last Update:

Interconnector Demand response Electric power systems components Ring main unit Grid-tie inverter Energy storage Busbar Bus duct Recloser Protective relay v t e...

Word Count : 723

Interconnector

Last Update:

Interconnector Demand response Electric power systems components Ring main unit Grid-tie inverter Energy storage Busbar Bus duct Recloser Protective relay v t e...

Word Count : 404

Power inverter

Last Update:

Interconnector Demand response Electric power systems components Ring main unit Grid-tie inverter Energy storage Busbar Bus duct Recloser Protective relay v t e...

Word Count : 6520

Photovoltaic system

Last Update:

relay desensitization, nuisance tripping, interference with automatic reclosers, and ferroresonance. Islanding is the condition in which a distributed...

Word Count : 13692

Islanding

Last Update:

However, it is neither clear that reclosers are still useful in modern utility practice nor that breaker-reclosers must act on all phases. Autorité de...

Word Count : 2704

Energy storage

Last Update:

Interconnector Demand response Electric power systems components Ring main unit Grid-tie inverter Energy storage Busbar Bus duct Recloser Protective relay v t e...

Word Count : 10960

Industrial internet of things

Last Update:

also manage other distribution automation devices like transformers and reclosers. As of 2016, other real-world applications include incorporating smart...

Word Count : 3546

Hubbell Incorporated

Last Update:

bushings Grounding equipment Cutouts & fuse links Insulators Programmable reclosers Pole line hardware Cable terminations & accessories Sectionalizers Helical...

Word Count : 1932

Demand response

Last Update:

Interconnector Demand response Electric power systems components Ring main unit Grid-tie inverter Energy storage Busbar Bus duct Recloser Protective relay v t e...

Word Count : 6800

PDF Search Engine © AllGlobal.net